September 06, 2007

SCADA : The control System

SCADA is the acronym for Supervisory Control And Data Acquisition. The term is used differently in North America than in the rest of the world:

  • In North America; SCADA refers to a large-scale, distributed measurement and control system.

  • In the rest of the world; SCADA is any system that performs Supervisory Control And Data Acquisition, independent of its size or geographical distribution.


SCADA systems are typically used to perform data collection and control at the supervisory level. Some SCADA systems only monitor without doing control, these systems are still referred to as SCADA systems.

The supervisory control system is a system that is placed on top of a real-time control system to control a process that is external to the SCADA system (i.e. a computer, by itself, is not a SCADA system even though it controls its own power consumption and cooling). This implies that the system is not critical to control the process in real-time, as there is a separate or integrated real-time automated control system that can respond quickly enough to compensate for process changes within the time-constants of the process. The process can be industrial, infrastructure or facility based as described below:

  • Industrial processes include: manufacturing/production/power generation/fabrication/refining - continuous, batch, repetitive or discrete.

  • Infrastructure processes may be public or private and include: water treatment and distribution, wastewater collection and wastewater treatment, oil & gas pipelines, electrical power transmission and distribution and large communication systems.

  • Facility processes in private or public facilities including: buildings, airports, ships or space stations in order to monitor and control: HVAC, access control, energy consumption management


The SCADA systems for these applications all perform Supervisory Control And Data Acquisition, even though the use of the systems are very different.









Systems concepts


A SCADA system includes input/output signal hardware, controllers, HMI, networks, communication, database and software. It mainly comes in the branch of Instrumentation Engineering.

The term SCADA usually refers to a central system that monitors and controls a complete site or a system spread out over a long distance (kilometres/miles). The bulk of the site control is actually performed automatically by a Remote Terminal Unit (RTU) or by a Programmable Logic Controller (PLC). Host control functions are almost always restricted to basic site over-ride or supervisory level capability. For example, a PLC may control the flow of cooling water through part of an industrial process, but the SCADA system may allow an operator to change the control set point for the flow, and will allow any alarm conditions such as loss of flow or high temperature to be recorded and displayed. The feedback control loop is closed through the RTU or PLC; the SCADA system monitors the overall performance of that loop.

Image:SCADA schematic overview-s.png

Data acquisition begins at the RTU or PLC level and includes meter readings and equipment statuses that are communicated to SCADA as required. Data is then compiled and formatted in such a way that a control room operator using the HMI can make appropriate supervisory decisions that may be required to adjust or over-ride normal RTU (PLC) controls. Data may also be collected in to a Historian, often built on a commodity Database Management System, to allow trending and other analytical work.

SCADA systems typically implement a distributed database, commonly referred to as a tag database, which contains data elements called tags or points. A point represents a single input or output value monitored or controlled by the system. Points can be either "hard" or "soft". A hard point is representative of an actual input or output connected to the system, while a soft point represents the result of logic and math operations applied to other hard and soft points. Most implementations conceptually remove this distinction by making every property a "soft" point (expression) that can equal a single "hard" point in the simplest case. Point values are normally stored as value-timestamp combinations; the value and the timestamp when the value was recorded or calculated. A series of value-timestamp combinations is the history of that point. It's also common to store additional metadata with tags such as: path to field device and PLC register, design time comments, and even alarm information.

It is possible to purchase a SCADA system or Distributed Control System (DCS) from a single supplier. It is more common to assemble a SCADA system from hardware and software components like ABB, Allen-Bradley, DirectLOGIC, GE Fanuc, Schneider Electric, or Siemens PLCs, along with related HMI packages from Adroit, Citect, GE Fanuc,Honeywell, ICONICS, Inductive Automation, Rockwell Automation, Schneider Electric, SUPCON, Telvent, or Wonderware.


Human Machine Interface


A Human-Machine Interface or HMI is the apparatus which presents process data to a human operator, and through which the human operator controls the process.

The HMI industry was essentially born out of a need for a standardized way to monitor and to control multiple remote controllers, PLCs and other control devices. While a PLC does provide automated, pre-programmed control over a process, they are usually distributed across a plant, making it difficult to gather data from them manually. Historically PLCs had no standardized way to present information to an operator. The SCADA system gathers information from the PLCs and other controllers via some form of network, and combines and formats the information. An HMI may also be linked to a database, to provide trending, diagnostic data, and management information such as scheduled maintenance procedures, logistic information, detailed schematics for a particular sensor or machine, and expert-system troubleshooting guides. Since about 1998, virtually all major PLC manufacturers have offered integrated HMI/SCADA systems, many of them using open and non-proprietary communications protocols. Numerous specialized third-party HMI/SCADA packages, offering built-in compatibility with most major PLCs, have also entered the market, allowing mechanical engineers, electrical engineers and technicians to configure HMIs themselves, without the need for a custom-made program written by a software developer.

SCADA is popular, due to its compatibility and reliability. It is used in small applications, like controlling the temperature of a room, to large applications, such as the control of nuclear power plants.


Hardware solutions


SCADA solutions often have Distributed Control System (DCS) components. Use of "smart" RTUs or PLCs, which are capable of autonomously executing simple logic processes without involving the master computer, is increasing. A functional block programming language, IEC 61131-3, is frequently used to create programs which run on these RTUs and PLCs. Unlike a procedural language such as the C programming language or FORTRAN, IEC 61131-3 has minimal training requirements by virtue of resembling historic physical control arrays. This allows SCADA system engineers to perform both the design and implementation of a program to be executed on a RTU or PLC.


System components


The three components of a SCADA system are:

  1. Multiple Remote Terminal Units (also known as RTUs or Outstations).

  2. Master Station and HMI Computer(s).

  3. Communication infrastructure



Remote Terminal Unit (RTU)


The RTU connects to physical equipment, and reads status data such as the open/closed status from a switch or a valve, reads measurements such as pressure, flow, voltage or current. By sending signals to equipment the RTU can control equipment, such as opening or closing a switch or a valve, or setting the speed of a pump.

The RTU can read digital status data or analog measurement data, and send out digital commands or analog setpoints.

An important part of most SCADA implementations are alarms. An alarm is a digital status point that has either the value NORMAL or ALARM. Alarms can be created in such a way that when their requirements are met, they are activated. An example of an alarm is the "fuel tank empty" light in a car. The SCADA operator's attention is drawn to the part of the system requiring attention by the alarm. Emails and text messages are often sent along with an alarm activation alerting managers along with the SCADA operator.


Master Station


The term "Master Station" refers to the servers and software responsible for communicating with the field equipment (RTUs, PLCs, etc), and then to the HMI software running on workstations in the control room, or elsewhere. In smaller SCADA systems, the master station may be composed of a single PC. In larger SCADA systems, the master station may include multiple servers, distributed software applications, and disaster recovery sites

The SCADA system usually presents the information to the operating personnel graphically, in the form of a mimic diagram. This means that the operator can see a schematic representation of the plant being controlled. For example, a picture of a pump connected to a pipe can show the operator that the pump is running and how much fluid it is pumping through the pipe at the moment. The operator can then switch the pump off. The HMI software will show the flow rate of the fluid in the pipe decrease in real time. Mimic diagrams may consist of line graphics and schematic symbols to represent process elements, or may consist of digital photographs of the process equipment overlain with animated symbols.

The HMI package for the SCADA system typically includes a drawing program that the operators or system maintenance personnel use to change the way these points are represented in the interface. These representations can be as simple as an on-screen traffic light, which represents the state of an actual traffic light in the field, or as complex as a multi-projector display representing the position of all of the elevators in a skyscraper or all of the trains on a railway. Initially, more "open" platforms such as Linux were not as widely used due to the highly dynamic development environment and because a SCADA customer that was able to afford the field hardware and devices to be controlled could usually also purchase UNIX or OpenVMS licenses. Today, all major operating systems are used for both master station servers and HMI workstations.


Operational philosophy


Instead of relying on operator intervention, or master station automation, RTUs may now be required to operate on their own to control tunnel fires or perform other safety-related tasks. The master station software is required to do more analysis of data before presenting it to operators including historical analysis and analysis associated with particular industry requirements. Safety requirements are now being applied to the system as a whole and even master station software must meet stringent safety standards for some markets.

For some installations, the costs that would result from the control system failing is extremely high. Possibly even lives could be lost. Hardware for SCADA systems is generally ruggedized to withstand temperature, vibration, and voltage extremes, but in these installations reliability is enhanced by having redundant hardware and communications channels. A failing part can be quickly identified and its functionality automatically taken over by backup hardware. A failed part can often be replaced without interrupting the process. The reliability of such systems can be calculated statistically and is stated as the mean time to failure, which is a variant of mean time between failures. The calculated mean time to failure of such high reliability systems can be in the centuries.


Communication infrastructure and methods


SCADA systems have traditionally used combinations of radio and direct serial or modem connections to meet communication requirements, although Ethernet and IP over SONET is also frequently used at large sites such as railways and power stations.

This has also come under threat with some customers wanting SCADA data to travel over their pre-established corporate networks or to share the network with other applications. The legacy of the early low-bandwidth protocols remains, though. SCADA protocols are designed to be very compact and many are designed to send information to the master station only when the master station polls the RTU. Typical legacy SCADA protocols include Modbus, RP-570 and Conitel. These communication protocols are all SCADA-vendor specific. Standard protocols are IEC 60870-5-101 or 104, Profibus and DNP3. These communication protocols are standardized and recognized by all major SCADA vendors. Many of these protocols now contain extensions to operate over TCP/IP, although it is good security engineering practice to avoid connecting SCADA systems to the Internet so the attack surface is reduced.

RTUs and other automatic controller devices were being developed before the advent of industry wide standards for interoperability. The result is that developers and their management created a multitude of control protocols. Among the larger vendors, there was also the incentive to create their own protocol to "lock in" their customer base. A list of automation protocols is being compiled here.

In latest days, the OPC or "OLE for Process Control" has become a wide an accepted solution for intercomunicating differente hardware and software, allowing communication even between devices originally not intended to be part of an industrial network.

There are also other protocols like Modbus TCP/IP that became widely accepted and are now the standard for many hardware manufacturers.


Future trends in SCADA


The trend is for PLC and HMI/SCADA software to be more "mix-and-match". In the mid 1990s, the typical DAQ I/O manufacturer offered their own proprietary communications protocols over a suitable-distance carrier like RS-485. Towards the late 1990s, the shift towards open communications continued with I/O manufacturers offering support of open message structures like Modicon MODBUS over RS-485, and by 2000 most I/O makers offered completely open interfacing such as Modicon MODBUS over TCP/IP. The primary barriers of Ethernet TCP/IP's entrance into industrial automation (determinism, synchronization, protocol selection, environment suitability) are still a concern to a few extremely specialized applications, but for the vast majority of HMI/SCADA markets these barriers have been broken.


Security issues


Recently, the security of SCADA-based systems has come into question as they are increasingly seen as extremely vulnerable to cyberwarfare/cyberterrorism attacks on several fronts.[1] [2]

In particular, security researchers are concerned about:

  • the lack of concern about security and authentication in the design, deployment and operation of existing SCADA networks

  • the mistaken belief that SCADA systems have the benefit of security by obscurity through the use of specialized protocols and proprietary interfaces

  • the mistaken belief that SCADA networks are secure because they are supposedly physically secured

  • the mistaken belief that SCADA networks are secure because they are supposedly disconnected from the Internet


Due to the mission-critical nature of a large number of SCADA systems, such attacks could, in a worst case scenario, cause massive financial losses through loss of data or actual physical destruction, misuse or theft, even loss of life, either directly or indirectly. Whether such concerns will cause a move away from the use of existing SCADA systems for mission-critical applications towards more secure architectures and configurations remains to be seen, given that at least some influential people in corporate and governmental circles believe that the benefits and lower initial costs of SCADA based systems still outweigh potential costs and risks.[citation needed] Recently, multiple security vendors, such as Check Point and Innominate, have begun to address these risks by developing lines of specialized industrial firewall and VPN solutions for TCP/IP-based SCADA networks.

SCADA as a System


There are many parts of a working SCADA system. A SCADA system usually includes signal hardware (input and output), controllers, networks, user interface (HMI), communications equipment and software. All together, the term SCADA refers to the entire central system. The central system usually monitors data from various sensors that are either in close proximity or off site (sometimes miles away).

For the most part, the brains of a SCADA system are performed by the Remote Terminal Units (sometimes referred to as the RTU). The Remote Terminal Units consists of a programmable logic converter. The RTU are usually set to specific requirements, however, most RTU allow human intervention, for instance, in a factory setting, the RTU might control the setting of a conveyer belt, and the speed can be changed or overridden at any time by human intervention. In addition, any changes or errors are usually automatically logged for and/or displayed. Most often, a SCADA system will monitor and make slight changes to function optimally; SCADA systems are considered closed loop systems and run with relatively little human intervention.

One of key processes of SCADA is the ability to monitor an entire system in real time. This is facilitated by data acquisitions including meter reading, checking statuses of sensors, etc that are communicated at regular intervals depending on the system. Besides the data being used by the RTU, it is also displayed to a human that is able to interface with the system to override settings or make changes when necessary.

SCADA can be seen as a system with many data elements called points. Usually each point is a monitor or sensor. Usually points can be either hard or soft. A hard data point can be an actual monitor; a soft point can be seen as an application or software calculation. Data elements from hard and soft points are usually always recorded and logged to create a time stamp or history

User Interface (HMI)


A SCADA system includes a user interface, usually called Human Machine Interface (HMI). The HMI of a SCADA system is where data is processed and presented to be viewed and monitored by a human operator. This interface usually includes controls where the individual can interface with the SCADA system.

HMI's are an easy way to standardize the facilitation of monitoring multiple RTU's or PLC's (programmable logic controllers). Usually RTU's or PLC's will run a pre programmed process, but monitoring each of them individually can be difficult, usually because they are spread out over the system. Because RTU's and PLC's historically had no standardized method to display or present data to an operator, the SCADA system communicates with PLC's throughout the system network and processes information that is easily disseminated by the HMI.

HMI's can also be linked to a database, which can use data gathered from PLC's or RTU's to provide graphs on trends, logistic info, schematics for a specific sensor or machine or even make troubleshooting guides accessible. In the last decade, practically all SCADA systems include an integrated HMI and PLC device making it extremely easy to run and monitor a SCADA system.

SCADA Software and Hardware Components


SCADA systems are an extremely advantageous way to run and monitor processes. They are great for small applications such as climate control or can be effectively used in large applications such as monitoring and controlling a nuclear power plant or mass transit system.

SCADA can come in open and non proprietary protocols. Smaller systems are extremely affordable and can either be purchased as a complete system or can be mixed and matched with specific components. Large systems can also be created with off the shelf components. SCADA system software can also be easily configured for almost any application, removing the need for custom made or intensive software development.

1. Introduction


On 20 Sept. 2000, the Finance Committee approved the proposal to negotiate a contract with ETM A.G. (Eisenstadt, Austria) for the supply of PVSS - ETM's SCADA - for developing the control systems of ALICE, ATLAS, CMS and LHCb. In addition the SCADA Working Group, that was set up by the CERN Controls Board, recommends PVSS as one of the SCADA products for the development of future control systems at CERN.


These decisions are the accomplishment of around thirteen person-years (FTE) of effort - spanning over more than three years - to identify and evaluate a proper industrial control system that copes with the extreme requirements of high energy particle physics experiments such as those of the LHC.


Widely used in industry for Supervisory Control and Data Acquisition of industrial processes, SCADA systems are now also penetrating the experimental physics laboratories for the controls of ancillary systems such as cooling, ventilation, power distribution, etc. More recently they were also applied for the controls of smaller size particle detectors such as the L3 muon detector and the NA48 experiment, to name just two examples at CERN.


SCADA systems have made substantial progress over the recent years in terms of functionality, scalability, performance and openness such that they are an alternative to in house development even for very demanding and complex control systems as those of physics experiments.



2. What does SCADA MEAN?


SCADA stands for Supervisory Control And Data Acquisition. As the name indicates, it is not a full control system, but rather focuses on the supervisory level. As such, it is a purely software package that is positioned on top of hardware to which it is interfaced, in general via Programmable Logic Controllers (PLCs), or other commercial hardware modules.


SCADA systems are used not only in industrial processes: e.g. steel making, power generation (conventional and nuclear) and distribution, chemistry, but also in some experimental facilities such as nuclear fusion. The size of such plants range from a few 1000 to several 10 thousands input/output (I/O) channels. However, SCADA systems evolve rapidly and are now penetrating the market of plants with a number of I/O channels of several 100 K: we know of two cases of near to 1 M I/O channels currently under development.


SCADA systems used to run on DOS, VMS and UNIX; in recent years all SCADA vendors have moved to NT and some also to Linux.



3. Architecture


This section describes the common features of the SCADA products that have been evaluated at CERN in view of their possible application to the control systems of the LHC detectors [1], [2].


3.1 Hardware Architecture

One distinguishes two basic layers in a SCADA system: the "client layer" which caters for the man machine interaction and the "data server layer" which handles most of the process data control activities. The data servers communicate with devices in the field through process controllers. Process controllers, e.g. PLCs, are connected to the data servers either directly or via networks or fieldbuses that are proprietary (e.g. Siemens H1), or non-proprietary (e.g. Profibus). Data servers are connected to each other and to client stations via an Ethernet LAN. The data servers and client stations are NT platforms but for many products the client stations may also be W95 machines. Fig.1. shows typical hardware architecture.





Hardware Architecture





 


Figure 1: Typical Hardware Architecture


 


3.2 Software Architecture

The products are multi-tasking and are based upon a real-time database (RTDB) located in one or more servers. Servers are responsible for data acquisition and handling (e.g. polling controllers, alarm checking, calculations, logging and archiving) on a set of parameters, typically those they are connected to.


Software Architecture


Figure 2: Generic Software Architecture


However, it is possible to have dedicated servers for particular tasks, e.g. historian, datalogger, alarm handler. Fig. 2 shows a SCADA architecture that is generic for the products that were evaluated.


3.3 Communications

Internal Communication


Server-client and server-server communication is in general on a publish-subscribe and event-driven basis and uses a TCP/IP protocol, i.e., a client application subscribes to a parameter which is owned by a particular server application and only changes to that parameter are then communicated to the client application.


Access to Devices


The data servers poll the controllers at a user defined polling rate. The polling rate may be different for different parameters. The controllers pass the requested parameters to the data servers. Time stamping of the process parameters is typically performed in the controllers and this time-stamp is taken over by the data server. If the controller and communication protocol used support unsolicited data transfer then the products will support this too.


The products provide communication drivers for most of the common PLCs and widely used field-buses, e.g., Modbus. Of the three fieldbuses that are recommended at CERN, both Profibus and Worldfip are supported but CANbus often not [3]. Some of the drivers are based on third party products (e.g., Applicom cards) and therefore have additional cost associated with them. VME on the other hand is generally not supported.


A single data server can support multiple communications protocols: it can generally support as many such protocols as it has slots for interface cards.


The effort required to develop new drivers is typically in the range of 2-6 weeks depending on the complexity and similarity with existing drivers, and a driver development toolkit is provided for this.


3.4 Interfacing

Application Interfaces / Openness


The provision of OPC client functionality for SCADA to access devices in an open and standard manner is developing. There still seems to be a lack of devices/controllers, which provide OPC server software, but this improves rapidly as most of the producers of controllers are actively involved in the development of this standard. OPC has been evaluated by the CERN-IT-CO group [4].


The products also provide




  • an Open Data Base Connectivity (ODBC) interface to the data in the archive/logs, but not to the configuration database,

  • an ASCII import/export facility for configuration data,

  • a library of APIs supporting C, C++, and Visual Basic (VB) to access data in the RTDB, logs and archive. The API often does not provide access to the product's internal features such as alarm handling, reporting, trending, etc.


The PC products provide support for the Microsoft standards such as Dynamic Data Exchange (DDE) which allows e.g. to visualise data dynamically in an EXCEL spreadsheet, Dynamic Link Library (DLL) and Object Linking and Embedding (OLE).


Database


The configuration data are stored in a database that is logically centralised but physically distributed and that is generally of a proprietary format.


For performance reasons, the RTDB resides in the memory of the servers and is also of proprietary format.


The archive and logging format is usually also proprietary for performance reasons, but some products do support logging to a Relational Data Base Management System (RDBMS) at a slower rate either directly or via an ODBC interface.


3.5 Scalability

Scalability is understood as the possibility to extend the SCADA based control system by adding more process variables, more specialised servers (e.g. for alarm handling) or more clients. The products achieve scalability by having multiple data servers connected to multiple controllers. Each data server has its own configuration database and RTDB and is responsible for the handling of a sub-set of the process variables (acquisition, alarm handling, archiving).


3.6 Redundancy

The products often have built in software redundancy at a server level, which is normally transparent to the user. Many of the products also provide more complete redundancy solutions if required.



4. Functionality


4.1 Access Control

Users are allocated to groups, which have defined read/write access privileges to the process parameters in the system and often also to specific product functionality.


4.2 MMI

The products support multiple screens, which can contain combinations of synoptic diagrams and text.


They also support the concept of a "generic" graphical object with links to process variables. These objects can be "dragged and dropped" from a library and included into a synoptic diagram.


Most of the SCADA products that were evaluated decompose the process in "atomic" parameters (e.g. a power supply current, its maximum value, its on/off status, etc.) to which a Tag-name is associated. The Tag-names used to link graphical objects to devices can be edited as required. The products include a library of standard graphical symbols, many of which would however not be applicable to the type of applications encountered in the experimental physics community.


Standard windows editing facilities are provided: zooming, re-sizing, scrolling... On-line configuration and customisation of the MMI is possible for users with the appropriate privileges. Links can be created between display pages to navigate from one view to another.


4.3 Trending

The products all provide trending facilities and one can summarise the common capabilities as follows:




  • the parameters to be trended in a specific chart can be predefined or defined on-line

  • a chart may contain more than 8 trended parameters or pens and an unlimited number of charts can be displayed (restricted only by the readability)

  • real-time and historical trending are possible, although generally not in the same chart

  • historical trending is possible for any archived parameter

  • zooming and scrolling functions are provided

  • parameter values at the cursor position can be displayed


The trending feature is either provided as a separate module or as a graphical object (ActiveX), which can then be embedded into a synoptic display. XY and other statistical analysis plots are generally not provided.


4.4 Alarm Handling

Alarm handling is based on limit and status checking and performed in the data servers. More complicated expressions (using arithmetic or logical expressions) can be developed by creating derived parameters on which status or limit checking is then performed. The alarms are logically handled centrally, i.e., the information only exists in one place and all users see the same status (e.g., the acknowledgement), and multiple alarm priority levels (in general many more than 3 such levels) are supported.


It is generally possible to group alarms and to handle these as an entity (typically filtering on group or acknowledgement of all alarms in a group). Furthermore, it is possible to suppress alarms either individually or as a complete group. The filtering of alarms seen on the alarm page or when viewing the alarm log is also possible at least on priority, time and group. However, relationships between alarms cannot generally be defined in a straightforward manner. E-mails can be generated or predefined actions automatically executed in response to alarm conditions.


4.5 Logging/Archiving

The terms logging and archiving are often used to describe the same facility. However, logging can be thought of as medium-term storage of data on disk, whereas archiving is long-term storage of data either on disk or on another permanent storage medium. Logging is typically performed on a cyclic basis, i.e., once a certain file size, time period or number of points is reached the data is overwritten. Logging of data can be performed at a set frequency, or only initiated if the value changes or when a specific predefined event occurs. Logged data can be transferred to an archive once the log is full. The logged data is time-stamped and can be filtered when viewed by a user. The logging of user actions is in general performed together with either a user ID or station ID. There is often also a VCR facility to play back archived data.


4.6 Report Generation

One can produce reports using SQL type queries to the archive, RTDB or logs. Although it is sometimes possible to embed EXCEL charts in the report, a "cut and paste" capability is in general not provided. Facilities exist to be able to automatically generate, print and archive reports.


4.7 Automation

The majority of the products allow actions to be automatically triggered by events. A scripting language provided by the SCADA products allows these actions to be defined. In general, one can load a particular display, send an Email, run a user defined application or script and write to the RTDB.


The concept of recipes is supported, whereby a particular system configuration can be saved to a file and then re-loaded at a later date.


Sequencing is also supported whereby, as the name indicates, it is possible to execute a more complex sequence of actions on one or more devices. Sequences may also react to external events.


Some of the products do support an expert system but none has the concept of a Finite State Machine (FSM).



5. Application Development


5.1 Configuration

The development of the applications is typically done in two stages. First the process parameters and associated information (e.g. relating to alarm conditions) are defined through some sort of parameter definition template and then the graphics, including trending and alarm displays are developed, and linked where appropriate to the process parameters. The products also provide an ASCII Export/Import facility for the configuration data (parameter definitions), which enables large numbers of parameters to be configured in a more efficient manner using an external editor such as Excel and then importing the data into the configuration database.


However, many of the PC tools now have a Windows Explorer type development studio. The developer then works with a number of folders, which each contains a different aspect of the configuration, including the graphics.


The facilities provided by the products for configuring very large numbers of parameters are not very strong. However, this has not really been an issue so far for most of the products to-date, as large applications are typically about 50K I/O points and database population from within an ASCII editor such as Excel is still a workable option.


On-line modifications to the configuration database and the graphics is generally possible with the appropriate level of privileges.


5.2 Development Tools

The following development tools are provided as standard:




  • a graphics editor, with standard drawing facilities including freehand, lines, squares circles, etc. It is possible to import pictures in many formats as well as using predefined symbols including e.g. trending charts, etc. A library of generic symbols is provided that can be linked dynamically to variables and animated as they change. It is also possible to create links between views so as to ease navigation at run-time.

  • a data base configuration tool (usually through parameter templates). It is in general possible to export data in ASCII files so as to be edited through an ASCII editor or Excel.

  • a scripting language

  • an Application Program Interface (API) supporting C, C++, VB

  • a Driver Development Toolkit to develop drivers for hardware that is not supported by the SCADA product.


5.3 Object Handling

The products in general have the concept of graphical object classes, which support inheritance. In addition, some of the products have the concept of an object within the configuration database. In general the products do not handle objects, but rather handle individual parameters, e.g., alarms are defined for parameters, logging is performed on parameters, and control actions are performed on parameters. The support of objects is therefore fairly superficial.



6. Evolution


SCADA vendors release one major version and one to two additional minor versions once per year. These products evolve thus very rapidly so as to take advantage of new market opportunities, to meet new requirements of their customers and to take advantage of new technologies.


As was already mentioned, most of the SCADA products that were evaluated decompose the process in "atomic" parameters to which a Tag-name is associated. This is impractical in the case of very large processes when very large sets of Tags need to be configured. As the industrial applications are increasing in size, new SCADA versions are now being designed to handle devices and even entire systems as full entities (classes) that encapsulate all their specific attributes and functionality. In addition, they will also support multi-team development.


As far as new technologies are concerned, the SCADA products are now adopting:




  • Web technology, ActiveX, Java, etc.

  • OPC as a means for communicating internally between the client and server modules. It should thus be possible to connect OPC compliant third party modules to that SCADA product.


7. Engineering


Whilst one should rightly anticipate significant development and maintenance savings by adopting a SCADA product for the implementation of a control system, it does not mean a "no effort" operation. The need for proper engineering can not be sufficiently emphasised to reduce development effort and to reach a system that complies with the requirements, that is economical in development and maintenance and that is reliable and robust. Examples of engineering activities specific to the use of a SCADA system are the definition of:




  • a library of objects (PLC, device, subsystem) complete with standard object behaviour (script, sequences, ...), graphical interface and associated scripts for animation,

  • templates for different types of "panels", e.g. alarms,

  • instructions on how to control e.g. a device ...,

  • a mechanism to prevent conflicting controls (if not provided with the SCADA),

  • alarm levels, behaviour to be adopted in case of specific alarms, ...


8. Potential benefits of SCADA


The benefits one can expect from adopting a SCADA system for the control of experimental physics facilities can be summarised as follows:




  • a rich functionality and extensive development facilities. The amount of effort invested in SCADA product amounts to 50 to 100 p-years!

  • the amount of specific development that needs to be performed by the end-user is limited, especially with suitable engineering.

  • reliability and robustness. These systems are used for mission critical industrial processes where reliability and performance are paramount. In addition, specific development is performed within a well-established framework that enhances reliability and robustness.

  • technical support and maintenance by the vendor.


For large collaborations, as for the CERN LHC experiments, using a SCADA system for their controls ensures a common framework not only for the development of the specific applications but also for operating the detectors. Operators experience the same "look and feel" whatever part of the experiment they control. However, this aspect also depends to a significant extent on proper engineering.